CSXi Specification
Mains Supply
Mains voltage (L1, L2, L3)
CSXi-xxx-V4
3 x 200 VAC ~ 440 VAC (+ 10% / - 15%)
CSXi-xxx-V6
3 x 200 VAC ~ 575 VAC (+ 10% / - 15%)
Mains frequency (at start)
45 Hz to 66 Hz
Rated insulation voltage
600 VAC
Form designation
Control Voltage (A1, A2, A3)
CSXi-xxx-xx-C1
110-240 VAC (+ 10% / - 15%) or 380-440 VAC (+ 10% / - 15%)
CSXi-xxx-xx-C2
24 VAC/VDC (± 20%)
Current consumption (during run)
< 100 mA
Current consumption (at power-up)
CSXi-xxx-xx-C1
10A
CSXi-xxx-xx-C2
2 A
Inputs
Start (terminals 01)
Normally Open, 300 VAC max
Stop (terminals 02)
Normally Closed, 300 VAC max
Outputs
Main Contactor (terminals 13, 14)
Normally Open
6 A, 30 VDC resistive / 2 A, 400 VAC, AC11
6 A, 30 VDC resistive / 2 A, 400 VAC, AC11
Programmable relay (terminals 23, 24)
Normally Open
6 A, 30 VDC resistive / 2 A, 400 VAC, AC11
6 A, 30 VDC resistive / 2 A, 400 VAC, AC11
Environmental
Degree of protection CSXi-007 to CSXi-055
IP20
Degree of protection CSXi-075 to CSXi-110
IP00
Operating temperatures
- 10 °C to + 60 °C
Humidity
5% to 95% Relative Humidity
Pollution Degree
Pollution Degree 3
Vibration
IEC 60068 Test Fc Sinusoidal
4 Hz to 13.2 Hz: ± 1 mm displacement
13.2 Hz to 200 Hz: ± 0.7 g
4 Hz to 13.2 Hz: ± 1 mm displacement
13.2 Hz to 200 Hz: ± 0.7 g
EMC Emission
Equipment class (EMC)
Class A
Conducted radio frequency emission
0.15 MHz to 0.5 MHz: < 90 dB (µV)
0.5 MHz to 5 MHz: < 76 dB (µV)
5 MHz to 30 MHz: 80-60 dB (µV)
0.5 MHz to 5 MHz: < 76 dB (µV)
5 MHz to 30 MHz: 80-60 dB (µV)
Radiated radio frequency emission
30 MHz to 230 MHz: < 30 dB (µV/m)
230 MHz to 1000 MHz: < 37 dB (µV/m)
230 MHz to 1000 MHz: < 37 dB (µV/m)
This product has been designed as Class A equipment. Use of this product in domestic environments may cause radio interference, in which case the user may be required to employ additional mitigation methods.
EMC Immunity
Electrostatic discharge
4 kV contact discharge, 8 kV air discharge
Radio frequency electromagnetic field
0.15 MHz to 0.5 MHz: < 90 dB (µV)
Rated impulse withstand voltage (Fast transients 5/50 ns)
2 kV line to earth, 1 kV line to line
Voltage dip and short time interruption
100 ms (at 40% nominal voltage)
Harmonics and distortion
IEC61000-2-4 (Class 3), EN/IEC61800-3
Short Circuit
Rated short-circuit current CSXi-007 to CSXi-037
5 kA
Rated short-circuit current CSXi-045 to CSX-i110
10 kA
Heat Dissipation
During Start
3 watts / ampere
During Run
10 watts typical
Approvals
C
IEC 60947 4 2
UL / C-UL
UL 508
CE
IEC 60947 4 2
CCC
GB 14048.6
Lloyds
IEC 60947 4 2