MVX Specification
Supply
Mains Voltage
MVXxxxx-V12
12 kV Phase-phase
Rated Frequency
50 Hz or 60 Hz
Rated Power Frequency Withstand Voltage (Ud)
MVXxxxx-V12
42 kV
Rated Lightning Impulse Withstand Voltage (Up)
MVXxxxx-V12
75 kV
Rated short-time withstand current (asymmetrical RMS peak) (Ik)
MVXxxxx-V12
31.5 kA for 4 seconds
Form Designation
Bypassed semiconductor motor starter form 1
Control Inputs
Start (Terminals C23, C24)
24 VDC, 8 mA approx
Stop (Terminals C31, C32)
24 VDC, 8 mA approx
Reset (Terminals C41, C42)
24 VDC, 8 mA approx
Input A (Terminals C53, C54)
24 VDC, 8 mA approx
Input B (Terminals C63, C64)
24 VDC, 8 mA approx
Motor Thermistor (Terminals B4, B5)
Trip point > 2.8 kOhm
Control Outputs
Relay Outputs
10 A @ 250 VAC resistive
6 A @ 250 VAC AC15 p.f. 0.3
10 A @ 30 VDC resistive
6 A @ 250 VAC AC15 p.f. 0.3
10 A @ 30 VDC resistive
Main Contactor (Terminals 13, 14)
Normally Open
Bypass Contactor (Terminals 23, 24)
Normally Open
Run Output/ PFC (Terminals 33, 34)
Normally Open
Output Relay A (Terminals 43, 44)
Normally Open
Output Relay B (Terminals 51, 52, 54)
Changeover
Output Relay C (Terminals 61, 62, 64)
Changeover
Analog Output (Terminals B10, B11)
0-20 mA or 4-20 mA
Environmental
Equipment Class (EMC)
Class A
Internal Arc Classification (IAC)
AFLR to maximum of 31.5 kA for 1 second
Degree of Protection
Phase Cassette
IP00
Controller
IP54/ NEMA 12
Operating Environment
IEC60721-3-3: IE34: Climatic 3K4
-5 °C to 40 °C, with derating to 55 °C
Relative Humidity
5% to 95%
Storage Environment
IEC60721-3-1: IE12
- 5 °C to + 45 °C
Relative Humidity
5% to 95%
Pollution Degree
Pollution Degree 2
Vibration
IEC 60068-2-6 Fc
Standards Approvals
C√
EMC requirements
CE
EMC EU Directive
MVX Protection Codes
Code | Protection description | MVX Protection (built-in) |
---|---|---|
48 | Maximum start time | Excess start time |
66 | Too many starts | Restart delay and dynamic thermal model |
37 | Undercurrent | |
51L | Load Increase (alarm) | High current frequency output |
51R | Overcurrent - jam | Excess start time, electronic shearpin |
50 | Overcurrent - short | Shorted SCR, electronic shearpin |
49/51 | Thermal overload | Thermal overload - dynamic model |
46 | Current imbalance | Current imbalance |
Positive/negative phase sequence | Phase sequence | |
27 | Undervoltage | Undervoltage |
59 | Overvoltage | Overvoltage |
47 | Phase loss | Phase loss |
47 | Phase sequence | Phase sequence |
50G | Ground fault | Ground fault |
3 | Communications failure | Communications failure |
3 | Internal failure | Internal failure |
86/97 | Ext. fault 1/code - 1 | Auxiliary trip A |
Ext. fault 1/code - 2 | Auxiliary trip B | |
38 | Motor overtemperature | Thermistor protection* |
49 | Stator winding overtemperature | Thermistor protection* |
32 | Under power | Power Loss |
* RTD Relay is an optional extra.